Initial Setting Level Section 5-7
• Select one of the following alarm 1 types:
Deviation, deviation range, absolute value, LBA, or PV change rate alarm.
Note (1) With set values 1, 4 and 5, the upper- and lower- limit values can be set
independently for each alarm type, and are expressed as “L” and “H.”
(2) Set value: 1 (Upper- and lower-limit alarm)
alt1 Alarm 1 Type
Alarm 1 must be assigned.
Set values Alarm type Alarm output operation
When alarm value X
is positive
When alarm value X
is negative
0 Alarm function OFF Output OFF
1 (See note
1.)
Upper- and lower-limit (See note 2.)
2 Upper-limit
3 Lower-limit
4 (See note
1.)
Upper- and lower-limit
range
(See note 3.)
5 (See note
1.)
Upper- and lower-limit
with standby sequence
(See note 4.)
6 Upper-limit with standby
sequence
7 Lower-limit with standby
sequence
8 Absolute-value upper-
limit
9 Absolute-value lower-limit
10 Absolute-value upper-
limit with standby
sequence
11 Absolute-value lower-limit
with standby sequence
12 LBA (alarm 1 type only) ---
13 PV change rate alarm ---
Function
Setting
LH
ON
OFF
SP
X
ON
OFF
SP
ON
OFF
SP
X
X
ON
OFF
SP
X
ON
OFF
SP
LH
ON
OFF
SP
LH
ON
OFF
SP