280
Appendix
(4-3) Initialized to the above default values regardless of the settings for changing the transfer out-
put type.
(5) Initialized as follows according to the Standard or Heating/Cooling parameter setting.
MV Upper Limit: 105.0
MV Lower Limit: Standard
−5.0, heating/cooling −105.0
(6) Initialized to control output (cooling) for heating and cooling control, according to the following.
(The defaults for standard control are the defaults in the parameter list.)
With control output 2: The Control Output 2 Assignment parameter is initialized to control output
(cooling).
Without control output 2 and E5AN/EN: The Auxiliary Output 3 Assignment parameter is initialized
to control output (cooling).
Without control output 2 and E5CN: The Auxiliary Output 2 Assignment parameter is initialized to
control output (cooling).
(7) When the program pattern is OFF, the Auxiliary Output 1 Assignment parameter is initialized to
alarm output 1. When the program pattern is not OFF, the Auxiliary Output 1 Assignment parameter
is initialized to program end output.
(8) When the program pattern is changed to OFF, if the Program Start parameter is assigned it is ini-
tialized to “not assigned.”
(9) Initialized when temperature inputs are used and RT is changed. The defaults are as follows:
Proportional band: 8.0
Integral time: 233
Derivative time: 40 when RT is OFF, and 40.0 when RT is ON.
(10) The proportional band, integral time, and derivative time are initialized as follows by RT and input
type changes.
• When RT is turned from ON to OFF by a change from temperature input to analog input.
• When ON is turned to OFF or OFF is turned to ON by an RT change.
(11) Write to both so that the SP and the currently selected Multi-SP SP0 to SP3 match.
(12) Initializes event input assignments used for Multi-SP to NONE.
(13) Initialized to 0.8 when the temperature unit is
°C, and to 1.4 when the temperature unit is °F.