6-3 PT Settings
6-24
1. Set the waiting time in the Start-up Wait Time field in second units.
Input the value in the dialog box that is displayed by pressing the setting input column.
2. After setting, press the Write Button to save the setting.
Reference • Nothing is displayed during the system startup waiting time.
• The system startup waiting time is calculated from when initialization finishes.
Therefore, if the startup waiting time is set to 0 s, the PT will not start actual communi-
cations with the host immediately after the power is turned ON.
6-3-2 Screen Saver
To extend the life of the backlight, the screen saver function turns OFF the screen display
when operations are not performed for a fixed period of time.
The default setting is for no screen saver.
The time before the screen saver function is activated can be set in one-minute units be-
tween 1 and 255 minutes. The default setting is 15 min.
Set the screen saver movement by using operations from the PT Tab Page in the System
Menu, as follows:
1. Select either OFF or Display Erased for the screen saver.
2. If Display Erased is selected, set the screen saver startup time.
Input the value in the dialog box that is displayed by pressing the setting input column.
3. After setting, press the Write Button to save the setting.
If the screen saver start-up time is set to Indirect Specification with the CX-Designer, the ad-
dress of the allocation destination will be displayed. The address of the allocation destination
will be displayed only. It cannot be changed.