Variable name _EIP2_TargetNodeErr[255]
Meaning CIP Communications2 Target Node Error Infor-
mation
Global/local Global
Function Indicates that the connection for the Registered Target Node Information for CIP communications 2 was not es-
tablished or that an error occurred in the target Controller
.
The array elements are valid only when the Registered Target Node Information is TRUE.
Array[x] is TRUE: A connection was not normally established with the target node for a target node ID of x (the
Registered Target Node Information is TRUE and the Normal Target Node Information is FALSE), or a connection
was established with the target node but an error occurred in the target Controller.
Array[x] is FALSE: The target node is not registered for a target node ID of x (the Registered Target Node Infor-
mation is FALSE), or a connection was normally established with the target node (the Registered Target Node
Information is TRUE and the Normal Target Node Information is TRUE). An error occurred in the target Controller
(the Target PLC Error Information is TRUE).
Note You can use this system-defined variable only for the NX701 CPU Units and NX102 CPU Units.
Data type ARRAY [0..255] OF BOOL Range of values TRUE or FALSE
R/W access R Retained Not retained. Network Publish Published.
Usage in user pro-
gram
Possible. Related in-
structions
---
Variable name _EIP_NTPResult Member name .ExecTime
Meaning NTP Last Operation Time Global/local Global
Function Gives the last time that NTP processing ended normally.
The time that was obtained from the NTP server is stored when the time is obtained normally
.
The time is not stored if it is not obtained from the NTP server normally.
Note Do not use this variable in the user program. There may be a delay in updating it. Use this vari-
able only to access status through communications from an external device.
Data type Structure: _sNTP_RESULT
Members: DA
TE_AND_TIME
Range of values Depends on data type.
R/W access R Retained Not retained. Network Publish Published.
Usage in user pro-
gram
Not possible. Related in-
structions
You can read the contents of this variable with the GetNTPStatus instruction.
Variable name _EIP_NTPResult Member name .ExecNormal
Meaning NTP Operation Result Global/local Global
Function This variable shows if the NTP operation ended normally.
TRUE: Indicates an NTP normal end.
F
ALSE:Indicates that NTP operation ended in an error or has not been executed even once.
Note Do not use this variable in the user program. There may be a delay in updating it. Use this vari-
able only to access status through communications from an external device.
Data type BOOL Range of values TRUE or FALSE
R/W access R Retained Not retained. Network Publish Published.
Usage in user pro-
gram
Not possible. Related in-
structions
You can read the contents of this variable with the GetNTPStatus instruction.
3 System-defined Variables Related to the Built-in EtherNet/IP Port
3-59
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User’s Manual (W506)
3-3 Specifications for Individual System-defined Varia-
bles
3

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron NX102-12 Series and is the answer not in the manual?

Omron NX102-12 Series Specifications

General IconGeneral
BrandOmron
ModelNX102-12 Series
CategoryController
LanguageEnglish

Related product manuals