9-23
9 Details on Servo Parameter Objects
G5-series AC Servomotors and Servo Drives User’s Manual (with Built-in EtherCAT Communications)
9-3 Vibration Suppression Settings
9
Set the method to switch among four damping control filters.
Explanation of Set Values
*1 The set value 1 and 2 are for manufacturer's use only. Users are not allowed to set 1 and 2 for this object.
Set damping frequency 1 to suppress vibration at the end of the load in damping control.
Measure the frequency of vibration at the end of the load and make the setting in units of 0.1 Hz.
The range of setting frequency is 1.0 to 200.0 Hz. The function is disabled if the setting is 0 to 0.9 Hz.
Refer to 11-5 Damping Control on page 11-17.
First set
Damping Frequency 1 (3214 hex). Then reduce the setting if torque saturation occurs or
increase the setting to increase operation speed. Normally, use a setting of 0.
The upper limit of the set value is restricted to the smaller value of the corresponding damping
frequency or (2000 damping frequency).
Refer to 11-5 Damping Control on page 11-17 for more information on settings.
Set
damping frequency 2 to suppress vibration at the end of the load in damping control.
Measure the frequency of vibration at the end of the load and make the setting in units of 0.1 Hz.
Setting frequency is 1.0 to 200.0 Hz. The function is disabled if the setting is 0 to 0.9 Hz.
Refer to 11-5 Damping Control on page 11-17 for more information on settings.
3213 hex
Damping Filter Selection
Setting range 0 to 3 Unit
Default setting
0 Data attribute B
Size 2 bytes (INT16) Access RW PDO map Not possible.
Set value Explanation
0 Up two damping filters, damping filters 1 and 2, can be used at the same time.
1
Reserved for manufacturer use
*1
2
Reserved for manufacturer use
*1
3 The damping filters are switched with position command direction.
Forward direction: Damping filters 1 / 3 enabled
Reverse direction: Damping filters 2 / 4 enabled
3214 hex
Damping Frequency 1
Setting range 0 to 2000 Unit 0.1 Hz
Default setting
0 Data attribute B
Size 2 bytes (INT16) Access RW PDO map Not possible.
3215 hex
Damping Filter 1 Setting
Setting range 0 to 1000 Unit 0.1 Hz
Default setting
0 Data attribute B
Size 2 bytes (INT16) Access RW PDO map Not possible.
3216 hex
Damping Frequency 2
Setting range 0 to 2000 Unit 0.1 Hz
Default setting
0 Data attribute B
Size 2 bytes (INT16) Access RW PDO map Not possible.
csp
pp
hm
csv
csp
pp
hm
csp
pp
hm
csp
pp
hm