EasyManua.ls Logo

Omron SYSDRIVE 3G3EV SERIES

Omron SYSDRIVE 3G3EV SERIES
95 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...

Note Minimize the total length (5 m or less) between the ground electrode and the
ground terminal, and also use a thick wire (1.25 m
2
or more). Leakage current
flows through the Inverter. Therefore, if the distance between the ground elec-
trode and the ground terminal is too long, potential on the ground terminal of the
Inverter will become unstable.
3-2-3 Wiring Control Circuit Terminals
The control signal line must be 50 m or less and must be separated from
the power line.
Wiring Sequence Input/Output Terminals
Wire the multi-function input1 terminals (S1 and SC) and the multi-function output 1 ter-
minals (PA and PC) as described below.
WirestobeUsed
Wire type Wire size Wire to be used
Single wire 0.5to1.25mm
2
Polyethylene-shielded cable
Stranded wire 0.5to0.75mm
2
y
y
Wiring Method
Wire each terminal as follows:
a) Loosen the terminal screw with a thin-slotted screwdriver.
b) Insert the wire from underneath the terminal block.
c) Tighten the terminal screw firmly.

Chapter 3

Table of Contents

Related product manuals