Note 2. If “0” (stall prevention during deceleration) is set in this constant, deceleration
time will be automatically lengthened to prevent overvoltage.
Explanation of Stall Prevention during Deceleration
Output
frequency
Deceleration time is controlled
to prevent overvoltage
Deceleration time
(Setting)
Time

Operation after Recovery from Power Interruption
Setting range 0, 1, 2 Factory setting 0
This constant is used to select the processing to be performed after recovery from an
instantaneous power interruption.
Value Description
0 Discontinues operation.
1 Continues operation only if power interruption is within 0.5 second.
2 Continues operation unconditionally (with no error output).
Note If “1” or “2” is selected to continue operation, the Inverter automatically searches
the motor speed (even when the motor is in a free-running state) and continues
smooth operation. This function is called the speed search function.
Explanation of Speed Search Function
Motor speed
Free-running state
Inverter starts operating
Time

Carrier Frequency
Setting range 1, 2, 3, 4 Factory setting 4 (10 kHz)
This constant is used to set a pulse-width-modulated (PWM) carrier frequency.
Value Carrier frequency
1 2.5 (kHz)
2 5 (kHz)
3 7.5 (kHz)
4 10 (kHz)
  
Chapter 4

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Omron SYSDRIVE 3G3EV SERIES and is the answer not in the manual?

Omron SYSDRIVE 3G3EV SERIES Specifications

General IconGeneral
BrandOmron
ModelSYSDRIVE 3G3EV SERIES
CategoryInverter
LanguageEnglish

Related product manuals