Note 5. If “4,” “5,” and “6” are set in n06, n07, and n08, respectively, eight-step speed
operation can be performed.
(Number of frequency references selected) =
1 + (multi-step speed command 1) + (multi-step speed command 2) x 2 + (multi-step speed
command 3) x 4
The bit of multi-step speed command n is set to 1 (when ON) or 0 (when OFF).
Example of Multi-step Speed Operation
Output frequency
Frequency reference 1
Frequency reference 2
Frequency reference 3
Frequency reference 4
Run command
tep speed command 1
t
ep speed command 2

Multi-Function Output Selection 1
Setting range 0to11 Factory setting 1 (operation in
progress)

Multi-function output selection 2
Setting range 0to11 Factory setting 2 (frequency
matching)
  