EasyManua.ls Logo

OneAccess Crocus CNV - Downloading with TMA

OneAccess Crocus CNV
168 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Alarm attributes Crocus CNV
128 Reference manual
9.2.3 Alarm signalling
If you do not have a central management system, you could perform alarm signalling with the alarm
contacts of the CN4 card nest (this applies only to the crocusIfConvNx64<Tt/Cv>).
Example
Suppose the following situation:
On a remote Crocus CNV TT the configChanged alarm of the crocusIfConvNx64Tt object is set to enabled in
the remoteAlarmMask. In other words: crocusIfConvNx64Tt /remoteAlarmMask/configChanged = enabled.
On a central Crocus CNV CV the remoteAlarm of the top object is set to enabled in the
alarmContactHighMask. In other words: crocusIfConvNx64Tt /alarmContactHighMask/remoteAlarm = enabled.
The high alarm contacts of the CN4 card nest are connected in a circuit with a light bulb.
Now the following happens:
Phase Situation Result
1 Someone changes the configuration of the
Crocus CNV TT.
On the Crocus CNV TT the configChanged
alarm becomes active.
2
On the Crocus CNV TT the configChanged
alarm is enabled in the remoteAlarmMask.
A remote alarm is sent to the Crocus CNV
CV.
3
On the Crocus CNV CV the remoteAlarm is
enabled in the alarmContactHighMask.
The high alarm contacts of the CN4 card
nest close.
4 The high alarm contacts of the CN4 card
nest close.
The light bulb lights up.

Table of Contents