EasyManua.ls Logo

Pacific Power Source UPC-3 - Page 65

Default Icon
135 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
SECTION 4 OPERATION
53
4.5.2.1 TIME BASED TRANSIENT EXAMPLE (cont)
Press 1, ENTER, 1, ENTER, 1, to select Waveform 1 on all three phases.
TRANSIENT: PRGM #4 SEGMENT #3 OF 3
T=0.07 Va=108 Vb=108 Vc=108
F=400 WFa=1 WFb=1 WFc=1
Press STORE, to save the transient sequence.
TRANSIENT EVENTS:
ENTER # OF TRANSIENT EVENTS 1
0 FOR INFINITE OR 1-65535.
Press 1, STORE, to cause only one transient event.
V/I METER:
FREQ=400.0 Va=108.0 Vb=108.0 Vc=108.0
SENSE=INT Vab=187.1 Vbc=187.1 Vca=187.1
MANUAL MODE Ia=00.0 Ib=00.0 Ic=00.0
If the UPC was previously executing program #4, it will now be in MANUAL MODE. This is because
program #4 has changed. To execute the transient you must first execute program #4. Press
PROGRAM, 4, ENTER, EXECUTE, to execute the program.
V/I METER:
FREQ=400.0 Va=108.0 Vb=108.0 Vc=108.0
SENSE=INT Vab=187.1 Vbc=187.1 Vca=187.1
PROGRAM #4 Ia=00.0 Ib=00.0 Ic=00.0
Press TRANS to execute the transient.
This is a MIL-STD-704D under voltage time based transient. See figure 4.5.2.1.

Table of Contents

Related product manuals