4 System sizing
4.1 Recommended Injector/DLFC/BLFC-Valve configuration
Brine
syst.
Tank
Diameter
Resin
volume
Injector DLFC BLFC
[in] L DF Color UF Color [gpm] DF [gpm] UF [gpm]
5800/
1650
6 5 - 8 000 Brown 000 Brown 1.2 0.125 0.125
7 9 - 14
8 15 - 21 1.5
9 25 - 28
30 2
10 35 - 40 00 Violet 00 Violet 2.4
12 45 - 50 3.5
55 0 Red 0 Red 0.25 0.25
13 60 - 65 4
14 70 - 85 1 White 1 White 5
90 - 100 2 Blue 2 Blue 0.50 0.50
16 105 - 115 3 Yellow 3 Yellow 7
Info
In upflow configuration, the injector cap is fitted with a pressure regulator set to 1.4 or
2bar.
4.2 Sizing a softener (single unit)
4.2.1 Parameters to be considered
Whenever installing a softener, it is preferable to have full water analysis to ensure the inlet water
content will not affect the resin bed.
Tip
Please consult your resin manufacturer specification!
To ensure that no additional pretreatment prior to softening is required.
The below sizing method can be applied for both residential and industrial softeners.
The sizing of a softener must be based upon certain parameters:
• inlet water hardness;
• peak flow rate and nominal flow rate;
• service velocity;
• salt dosage.