2.4 STARTING THE NGC30
2.4.1 SYSTEM REQUIREMENTS
The minimum configuration to use the Raychem NGC-30 software is:
Raychem NGC-UIT2 hardware
At least one of the following:
NGC-30-CRM/-CRMS
RMM2 Remote Monitoring Module
RMC Module
NGC-20 Controller
Maximum optional equipment configuration:
Up to 52 Heat Trace Controller Boards (total count in any combination)
– NGC-30-CRM
– NGC-30-CRMS
Up to 16 RMM2 modules (8 channel RTD multiplexing hubs)
Up to 4 PLI modules (127 RTDs if SES/SPC transmitters are used, or 255 RTDs if 700-TT
transmitters are used)
Up to 247 NGC-20 controllers
Up to 247 RMM-DI modules
Total combination of output devices including NGC-30-CRM/-CRMS, NGC-20 and RMC DO cannot
exceed 260 circuits.
2.4.2 INITIAL SETUP
The Raychem NGC-30 software is designed to run only on the NGC-UIT2 hardware platform.
Prior to shipment, the Raychem NGC-30 software is installed into a nonvolatile area of the NGC-
UIT2 memory. During the initial power-up, you will see a blue background “splash” window for
approximately 30 seconds as the system software is loaded and initializes.