SECTION 3  FULL CONFIGURATION
3.1 SETTING THE NETWORK FOR DEVICES
Go to the Network|Device window.
For the very first time, the Network screen will be blank. See below:
Fig. 3.1 Initial Network|Device window
Press "Update Network" and scan all NGC-30-CRM/-CRMS boards, RMM2 module and others
into the Network database. The Device Addresses for these modules will be scanned and a
database will be created. A device address is the number assigned via the rotary switches on the
NGC-30-CRM/-CRMS board, RMM2 module, PLI Module, RMC module and RMM-DI module. If an
expected device does not appear on the list after the scan is complete, it is most likely physically
disconnected from the RS-485 network wiring, or is not powered. Troubleshoot and verify all
network and power connections.
Once the database exists, no further scanning is done unless the system is forced to update the
network by activating the "Update Network" button.
IMPORTANT: If a new external hardware device is added after the initial scan, you must initiate a
manual scan by going to the Network|Devices window and pressing the "Update Network" button.