If a PLI (Power Line Carrier Interface) module is detected in the scanning process, a pop-up
window will open, asking whether the PLI Mode should be changed from the default mode of
PLI-SES/SPC to the PLI-TT. If a SES or SPC Transmitter is connected to the PLI module, the
option "NO" should be selected. The NGC-30 UIT2 indicates this PLI as PLI-SES/SPC. If a 700-TT
Transmitter is connected to the PLI module, the option "YES" should be selected. The NGC-30
UIT2 indicates this PLI as PLI-TT.
Fig. 3.2 Set PLI Mode
IMPORTANT: The NGC-30 Control System can support up to 4 PLI Modules. Each PLI module can
support up to 127 SES or SPC transmitters and up to 255 700-TT transmitters. The SES/SPC and
700-TT transmitters are not compatible and can not be connected to the same PLI module
The Network will then be updated with the connected devices, in this case with one NGC-30-CRMS
board, one RMM2 and one PLI-SES/SPC modules.
Fig. 3.3 Connected Network|Devices window