The System|Password window provides the following controls:
• Level 1 - Allows setup of all configuration windows except for the System | Maint. window. This
Level 1 password is left “blank” from the factory; however, it can be set to a new designated
password. If a Level 1 password is chosen, the “Main Menu” timer value determines how long
the password remains active before it has to be re-entered. The password is limited to 40
characters.
• New Password Entry Field - Enter the user-defined password.
• Save new Password Action Button - Confirms password has been saved.
– Default: Level 1 disabled
• Level 2 - Allows access to System | Maintenance window, which permits clearing of Events and
program exit.
– The default password is 1234.
IMPORTANT: Change the Level 2 password after commissioning.
Old Password Entry Field
1234
New Password Entry Field
Enter your user-defined Level 2 password.
Save new Password Action Button
Confirms password has been saved.
IMPORTANT: Save and protect the Level 2 password in a secure location. Contact a Pentair
Industrial Heat Tracing Solutions representative for lost password recovery.
3.3.36 SYSTEM | MAINT. WINDOW
(Level 2 Password Required) This window allows for clearing the Events List and to exit the
program.
Fig. 3.49 System |Maint window