The 5 VDC sensor supply provides power to all 5
VDC sensors. The ECM supplies 5 VDC to terminal
3 of the fuel rail pressure sensor connector and to
terminal 1 of all other active sensor connectors. The
sensor common from the ECM connector goes to
terminal 1 of the connector for the fuel rail pressure
sensor. The sensor common from the ECM
connector goes to terminal 2 of all other active
sensor connectors. The sensor supply is output short
circuit protected. A short circuit to the battery will not
damage the circuit inside the ECM.
Pull-up Voltage
The ECM continuously outputs a pull-up voltage on
the circuit for the sensor signal wire. The ECM uses
this pull-up voltage to detect an open in the signal
circuit. When the ECM detects a voltage above a
threshold on the signal circuit, an open circuit
diagnostic code (XXXX-3) is generated for the
sensor.
If the sensor is disconnected, pull-up voltage
indicates that the wires from the sensor connector to
the ECM are not open or shorted to ground. If the
sensor is disconnected, the absence of pull-up
voltage indicates an open in the signal wire or a short
to ground. If the sensor is disconnected and the
voltage is different from pull-up voltage, the signal
wire is shorted to another wire in the harness.
384 UENR4469-36