Table 249
Troubleshooting Test Steps Values Results
1. Reset the Operator Inducement Emergency Override
A. Connect the electronic service tool to the diagnostic
connector.
B. Under the Service Tab , navigate to Operator Inducement
Emergency Override Timer Reset .
C. Click the Reset button at the bottom of the screen.
Reset Result: The Emergency Inducement Operator Override
Reset was performed.
Return the unit to service.
520 UENR4469-36
Service
Copyright of Perkins Engine Company Limited. NOT FOR REPRINTING OR RESALE