Display Description Remedy
0D10
to 0D13
An INTERBUS device is missing. Compare the bus topology with the current con-
figuration. If they match, check the segment for:
Shielding of bus cables or connectors, ground-
ing/equipotential bonding, defective connectors
or soldered joints, voltage dips on the logic volt-
age supply of the local bus device.
0D14
to 0D17
Multiple error in the segment of the specified device due to trans-
mission errors.
0D18
to 0D1B
Multiple timeout in the segment of the specified device due to trans-
mission errors.
0D1C
to 0D1F
Transmission error (CRC error) in the forward data path at the in-
coming bus interface (IN) of the specified device.
0D20
to 0D23
Interruption in the forward data path at the incoming bus interface
(IN) of the specified device.
0D24
to 0D27
Transmission error (CRC error) in the return data path at the incom-
ing bus interface (IN) of the specified device.
For Loop devices: Transmission path from the last Loop device to
the bus terminal module (BK).
0D28
to 0D2B
Interruption in the return data path at the incoming bus interface
(IN) of the specified INTERBUS device.
For Loop devices: Transmission path from the last Loop device to
the bus terminal module (BK).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Phoenix Contact IBS ABB DSC-T and is the answer not in the manual?

Phoenix Contact IBS ABB DSC-T Specifications

General IconGeneral
BrandPhoenix Contact
ModelIBS ABB DSC-T
CategoryController
LanguageEnglish

Related product manuals