50
5277A
0D2C
to 0D2F
Permanent error in the forward data path of the specified Loop de-
vice or error in the preceding Loop device.
Compare the bus topology with the current con-
figuration. If they match, check the segment for:
Bus cables, connectors or devices.0D30
to 0D33
Permanent error in the return data path from the last Loop device
to the bus terminal module (BK) or in the specified device.
Display Description Remedy