57
5277A
Display Description Remedy
0C80
to 0C83
0D80
to 0D83
Multiple error at the outgoing bus interface (OUT1) of the specified
INTERBUS device due to a defect taking place at the bus cable
connected, a defective following device or a defective device of
any subsequent local bus.
Check the shielding of bus cables or connectors,
grounding/equipotential bonding, defective con-
nectors or soldered joints, voltage dips on the
logic voltage supply of the remote bus devices.
0C84
to 0C87
0D84
to 0D87
Multiple timeout at the outgoing bus interface due to a defect taking place at the bus cable connected, a defective fol-
lowing device or a defective device of any subsequent local bus.
0C88
to 0C8B
0D88
to 0D8B
Unexpected devices were found at the outgoing bus interface (OUT1) of the specified device, e.g. devices connected
without an entry in the active configuration or INTERBUS cables connected without any further devices.
0C8C
to 0C8F
0D8C
to 0D8F
Only ID cycles but no data cycles can be run. The data register of the outgoing remote bus interface (OUT1) of the
specified device is interrupted or the number of data registers of the device that is connected to the outgoing remote
bus interface (OUT1) of the specified device is not identical with the length code.