5277A
0C90
to 0C93
The specified device could not activate the following bus segment,
as the device carried out a voltage reset or is defective.
a) Check the device.
b) Check the power supply of the device whether
it conforms to the nominal value and whether the
permissible AC voltage portion is exceeded (data
sheet).
c) Check the power supply unit of the bus termi-
nal module (BK) for overload (data sheet).
0C94
to 0C97
A device with the ID code of a local bus device was found at the outgoing remote bus interface of the specified device.
0C98
to 0C9B
0D98
to 0D9B
The device connected to the outgoing remote bus interface (OUT1) of the specified device has an invalid ID code.
0D9C
to 0D9F
The local bus connected directly to the controller board consists of more devices than were entered in the active con-
figuration.
Display Description Remedy