62
5277A
0CD0
to 0CD3
0DD0
to 0DD3
After the branching bus interface (OUT2) of the specified device
was opened (due to a firmware or hardware error) further devices
in addition to a bus terminal module (BK) were included in the data
ring.
Please contact Phoenix Contact.
0CD4
to 0CD7
0DD4
to 0DD7
Error in the 8-wire local bus connected to the specified device due
to a defective device in the local bus, defective local bus cable or
failure of the logic voltage V
L
.
Check the local bus.
0CD8 to
0CDB
0DD8 to
0DDB
The local bus connected to the specified bus terminal module (BK) consists of more local bus devices than were en-
tered in the active configuration.
0CDC to
0CDF
0DDC to
0DDF
The device connected to the branching bus interface (OUT2) of the specified device has an invalid ID code.
Display Description Remedy