Transmission error at OUT2. The SUPI3 detected a CRC or MAU (Medium Attachment Unit) error.
0C68
to 0C6B
0D68
to 0D6B
The SUPI3 of the specified device detected an I/O timeout.
0C6C
to 0C6F
0D6C
to 0D6F
The specified device carried out a reset due to a defect or an insuf-
ficient power supply.
Check the device. Check the power supply
whether it conforms to the nominal value and the
permissible AC voltage portion is exceeded (data
sheet). Check the power supply unit of the bus
terminal module (BK) for overload (data sheet).
0C70
to 0C73
0D70
to 0D73
The data transmission was aborted, as the INTERBUS device is
defective or the SUPI initialization failed.
a) Replace the INTERBUS device.
b) Delay the call of the Activate_Configuration_
Request (0711
hex
) service until the microproces-
sor has initialized the SUPI.
0D74
to 0D77
The data transmission was aborted. An invalid mode is set on the
Loop chip of an Loop device.
Please contact Phoenix Contact.