73
5277A
Display Description Remedy
0903 Not enough free memory space on the controller board. Carry out a warm start with the Reset_
Controllerboard_Request (0956
hex
) service.
0904 Inconsistent parameters were entered. Check the parameters entered last for inconsis-
tencies.
0905 Invalid parameters were entered. Check the parameters of the service called last.
0906 Access to this object is not supported. Check the last access.
0907 Attempt to access an object that does not exist.
0908 The service called conflicts with another services called before. Wait for the completion of the service called be-
fore, then try again.
0909 The confirmation which follows a service exceeds the maximum
permissible mailbox size.
Please contact Phoenix Contact.
090A The Parameter_Count parameter does not correspond to the number of subsequent words.
090B The controller board could not enable the specified service (wrong
password).
Use the right password or a service which is not
disabled.
0910 The service is disabled and cannot be called. Enable the service before calling, or use a ser-
vice which is not disabled.
0911 The controller board cannot enable the specified service (as it has
already been enabled).
Call the service.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Phoenix Contact IBS ABB DSC-T and is the answer not in the manual?

Phoenix Contact IBS ABB DSC-T Specifications

General IconGeneral
BrandPhoenix Contact
ModelIBS ABB DSC-T
CategoryController
LanguageEnglish

Related product manuals