89
5277A
0BD1 A data cycle exceeded the specified PD cycle time. The controller
board indicates this only, if it has been activated before with the
Set_Value_Request 0750
hex
service.
Check the system or increase the value set for
the PD cycle time with the Set_Value_Request
service.
0BD2 The bus warning time has elapsed. No data cycle could be trans-
mitted within the specified bus warning time.
Check the system or increase the bus warning
time with the Set_Value_Request service.
0BD4 A single bus error occurred. The controller board indicates this only if this function has been activated before.
0BDE A synchronization error occurred in the "bus synchronous" mode. Check the system or increase the value set for
the PD cycle time with the Set_Value_Request
service.
0BDF A bus error occurred. The controller board has stopped the data
transmission and is searching for the error location and cause.
Wait for the result of the troubleshooting.
Display Description Remedy