Commissioning
OperatingManualPNOZs50
1002194EN02
43
Function Terminal Description Parameter Value Indisplaymenu
Supplyvoltage,
powercircuits1
and2
B1/B2 Supplyvoltage InputVoltage 24V Input>InputVoltage
Testpulses Y1/Y2 Testpulsesonfeed
backloops
Pulsing On Feedback>Pulsing
>
Y1/Y2Pulse
Powercircuit1 O1+/O1 Reducedvoltage U 6V Output>O1
Overexcitationtime T 100ms Output>O1
Y1 Maximumventilation
time
Ton 30ms Feedback>Y1>
Y1Timing>Y1Ton
Maximumapplication
time,fastshutdown
Tofffast 30ms Feedback>Y1>
Y1Timing>Y1Toff
Maximumapplication
time,slowshutdown
Toffslow 30ms Feedback>Y1>
Y1Timing>Y1Toff
Logicoffeedbackloop
1
Logic N/C Feedback>Y1>
Logic>Y1Logic
Powercircuit2 O2+/O2 Reducedvoltage U 6V Output>O2
Overexcitationtime T 100ms Output>O2
Y2 Maximumventilation
time
Ton 30ms Feedback>Y2>
Y1Timing>Y2Ton
Maximumapplication
time,fastshutdown
Tofffast 30ms Feedback>Y2>
Y1Timing>Y2Toff
Maximumapplication
time,slowshutdown
Toffslow 30ms Feedback>Y2>
Y1Timing>Y2Toff
Logicoffeedbackloop
2
Logic NC Feedback>Y2>
Logic>Y2Logic
INFORMATION
Thedevicemustberestartediftheconfigurationhasbeenchanged(see
sectionentitled"Restartdevice").