Overview Displayformat Description
Y1TonorY2Ton
Configuremax.
ventilationtimefor
fastandslowshut
down
Y1 Ton
Fast / Slow
_ _ _ _ ms
Cancel Store
Y2 Ton
Slow/Fast<500>msMax.ventilation
time
Values:30…4000msconfigurablein
steps
Themax.ventilationtimesarethesame
forfastandslowshutdown.
Cancel–Exitmenuwithoutconfirmingthe
entry
Store–Confirmentry
Y1TofforY2Toff
Configuremax.ap
plicationtimefor
fastandslowshut
down
Y1 Toff
Fast _ _ _ _ ms
Slow _ _ _ _ ms
Cancel Store
Y2 Toff
Fast<500>msMax.applicationtime
forfastshutdown
Slow<500>msMax.applicationtime
forslowshutdown
Values:30…4000msconfigurablein
steps
Cancel–Exitmenuwithoutconfirmingthe
entry
Store–Confirmentry
ConfigurepowercircuitsO1+/O1andO2+/O2
Output
Configurepower
circuits
O1–SwitchtotheO1menutoconfigure
powercircuit1
O2–SwitchtotheO2menutoconfigure
powercircuit2
O1orO2
Configureoverex
citationtimeandre
ducedvoltage
O1
T _ _ _ _ ms
U _ _ _ _ V
Cancel Store
O2
O1orO2
T<1000>ms–Configureoverexcitation
time,values:off,100…2500msconfigur
ableinsteps.
If"off"isconfigured,thevoltageatB1/B2
isconnecteddirectlytooutputsO1orO2
withoutreduction.Anyvalueenteredfor
thereducedvoltagewillnotbeevaluated.
U<12>V–Configurereducedvoltage,
values:6,8,12,16,24V
Store–Confirmentry
Cancel–Exitmenuwithoutconfirmingthe
entry
Configurecounter
Counter
Specifyoffsetfor
numberofopera
tions
Counter
Counter 1
Counter 2
Counter1–Eventcounter1Switchto
theCounter1menutoconfigurethenum
berofoperationsforpowercircuitO1+/
O1
Counter2–Eventcounter2Switchto
theCounter2menutoconfigurethenum
berofoperationsforpowercircuitO2+/
O2