Commissioning
OperatingManualPNOZs50
1002194EN02
45
Overview Displayformat Description
InputVoltage
Configurethesup
plyvoltagetothe
powercircuits
Input Voltage
B1/B2
U 24 V
Cancel Store
U<24>VSelectsupplyvoltagefor
powercircuit,values:24,48V
Cancel–Exitmenuwithoutconfirmingthe
entry
Store–Confirmentry
ConfigurefeedbackloopsY1andY2
Feedback
Configurefeedback
loops
Pulsing–Configuretestpulses
Y1–SwitchtotheY1menutoconfigure
feedbackloopY1
Y2SwitchtotheY2menutoconfigure
feedbackloopY2
Y1/Y2Pulse
Activatetestpulse
Y1/Y2 Pulse
Pulse On/Off
Cancel Store
PulseOn:Testpulseon
PulseOff:Testpulseoff
Cancel–Exitmenuwithoutconfirmingthe
entry
Store–Confirmentry
Pleasenote:Thetestpulsescanonlybe
activatedsimultaneouslyforbothfeedback
loopsY1andY2.
Y1orY2
Switchtosub
menusforconfigur
ationofthefeed
backloops
Logic–SwitchtoLogicY1orLogicY2
menu
TimingSwitchtoTimingY1orTiming
Y2menu
Y1LogicorY2Lo
gic
DefineN/CorN/O
contactinthefeed
backloop
Y1 Logic
Logic N/O / N/C
Cancel Store
Y2 Logic
Logic<N/O/N/C>Inputlogicforfeed
backloopY1orY2:
N/O:N/Ocontact
N/C:N/Ccontact
Cancel–Exitmenuwithoutconfirmingthe
entry
Store–Confirmentry
Y1TimingorY2
Timing
Y1 Timing
Ton
Toff
Y2 Timing
Ton–Switchtosubmenuforconfiguration
ofthemax.ventilationtime
Toff–Switchtosubmenuforconfiguration
ofthemax.applicationtime