Operation
OperatingManualPNOZs50
1002194EN02
50
Cat. No. Errormessage Description Remedy
0 2 EnterStop Systemisin"STOP"state Purelyforinformation
0 3 EnterRun Systemisin"RUN"state Purelyforinformation
1 0 ACKIOFault The"IOFault"errorhasbeenre
setwiththeinputsY10/Y11and/
orY20/Y21(1/0pulseedge)
Purelyforinformation
4 0 CopyConfig Theconfigurationhasbeen
loadedfromthechipcardtothe
device.
Purelyforinformation
4 1 CopyConfig Thedevicehassavedtheconfig
urationtothechipcard.
Purelyforinformation
4 2 MissingCard Thereisnochipcardinthecard
slot.
Insertavalidchipcardintothe
cardslot
4 3 InvalidCard Thedataonthechipcardisin
valid
Checkchipcard
Insertavalidchipcardintothe
cardslot
4 4 Mems.Differ Thedataonthechipcarddiffers
fromthedatainthedevice
Useachipcardcontainingthe
deviceconfiguration
Writethedeviceconfigurationto
chipcard
4 5 CardRemoved Thechipcardhasbeenremoved
duringoperation
Insertavalidchipcardintothe
cardslot
4 6 UnknownCard Thechipcarddoesnotcontain
devicedataforthePNOZs50
Insertavalidchipcardintothe
cardslot
5 0 WrongPin Thepasswordisinvalid Enteravalidpassword
5 1 PinChanged Thepasswordhasbeen
changed
Purelyforinformation
5 2 Count.atMax Theeventcounterhasreached
themaximumvalue99999999.
Theeventcounterisnotreset
automatically.
Reseteventcounter
5 3 Chan.Differ Errorinthedevice'sparameter
settings
Checkparametersettings
6 0 SupplyNOK SupplyvoltageB1/B2tothe
powercircuitsisoutsidetheper
mittedrange.
Parameter1:
0x000000002
Checkthesupplyvoltage
6 1 SupplyOK SupplyvoltageB1/B2tothe
powercircuitsisonceagain
withinthepermittedrange.
Parameter1:
0x000000002
Purelyforinformation
7 0 ResetConfig Thedevicehasbeenresettoits
defaultsettings.
Purelyforinformation