14 Classification in accordance with ZVEI, CB24I
The following tables describe the classes and specific values of the product interface and
the classes of interfaces compatible with it. The classification is described in the ZVEI posi-
tion paper "Classification of Binary 24 V Interfaces - Functional Safety aspects covered by
dynamic testing".
Inputs
Drain Source
Safety switch C2 Safety control system C2, C3
Drain parameters Min. Typ. Max.
Test impulse duration - - 500 µs
Input resistance 5 kOhm - -
Capacitive load - - 1 nF
Test impulse interval 2 ms - -
Solenoid inputs
Drain Source
Safety switch C2 Safety control system C2, C3
Drain parameters Min. Typ. Max.
Test impulse duration - - 500 µs
Input resistance 3 kOhm -
Capacitive load - - 1,5 nF
Safe 1-pole SC outputs
Source Drain
Safety switch C2 Evaluation device C2
Parameter source Min. Typ. Max.
test pulse duration - - 450 µs
Max. ratio t
i
/T - - 5 %
Rated current - - 0,1 A
Capacitive load - - 70 nF