Connection to control systems and evaluation devices
Operating Manual PSENmlock mini, PSEN mlm 1 sa 1.1/2.1/2.2
1005802-EN-02-Draft
| 33
7.3 Single connection
24 V
0 V
A1
A2
12
22
I2 (FS)
I1 (FS)
FS: Failsafe
A1
A2
S31
S41
Y32
O2 (FS)
O1 (FS)
I1
S11
S21
Actuator
Safety switch
Safety controller
Activation of guard locking
7.4 Series connection
NOTICE
Extension of delay-on de-energisation
When several (n) devices are connected in series, the delay-on de-ener-
gisation time is multiplied by the number of interconnected safety switches.
The max. delay-on de-energisation is made up of the
risk time (see Technical details [
63])
+ (n-1) x max. delay-on de-energisation of the safety inputs
+ max. delay-on de-energisation of the evaluation device.
NOTICE
Increased current at the solenoid input
When several (n) devices are connected in series, the input current is multi-
plied by the number of safety switches connected in series (see Technical
details [
63]).