PowerLogic
®
Series 800 Power Meter 63230-500-224A1
Chapter 3—Installation 6/2006
EN–14
ENGLISH
For European Community (CE) compliance, the disconnect circuit
breaker must be placed within reach of the power meter and
labeled: Disconnect Circuit Breaker for Power Meter.
NOTE: The disconnect circuit breaker must be rated for the short
circuit current at the connection points.
Locate the power meter in an area where ambient conditions fall
within the acceptable range. For control power voltages above
300 Vac, the temperature range for the meter block is -25°C to
+65°C. The front display has a range of -10°C to +50°C.
NOTE: Ambient temperature refers to the immediate environment
of the power meter, including the temperature within the
enclosure in which it is mounted.
CAUTION
IMPROPER VENTILATION
Only mount the power meter as described in this instruction
bulletin.
Provide the clearances around the power meter as illustrated in
Figure 3 1, Figure 3 2, and Figure 3 3.
Failure to follow this instruction can result in equipment damage.