Chapter 3—Installation 6/2006
EN–14
ENGLISH
• For European Community (CE) compliance, the disconnect circuit
breaker must be placed within reach of the power meter and
labeled: Disconnect Circuit Breaker for Power Meter.
NOTE: The disconnect circuit breaker must be rated for the short
circuit current at the connection points.
• Locate the power meter in an area where ambient conditions fall
within the acceptable range. For control power voltages above
300 Vac, the temperature range for the meter block is -25°C to
+65°C. The front display has a range of -10°C to +50°C.
NOTE: Ambient temperature refers to the immediate environment
of the power meter, including the temperature within the
enclosure in which it is mounted.
CAUTION
IMPROPER VENTILATION
• Only mount the power meter as described in this instruction
bulletin.
• Provide the clearances around the power meter as illustrated in
Figure 3 – 1, Figure 3 – 2, and Figure 3 – 3.
Failure to follow this instruction can result in equipment damage.