Parameters | Determining factors
User Manual | Agrónic 2500
5.6.2 Conditional stop
For the associated programs while the determining
factor is active. When it becomes inactive, it continues
with the program at the point where it was.
Detection delay (0000 ... 9999”): the time that the deter-
mining factor must remain to activate or deactivate the
determining factor.
Origin: digital sensor
The determining factor is activated when the digital
sensor is activated for a period of time.
Origin: analog sensor
Reference: sensor value from which the determining
factor is activated or deactivated.
Dierential: margin between activation and deactiva-
tion of the determining factor.
When surpassed (Yes ... No):
• yes: if (value>reference) active determining factor.
If (value < reference – dierential) non-active
determining factor.
• No: if (value < reference) active determining factor.
If (value > reference + dierential) non-active
determining factor.
Origin: communication
Use the communication status with the AgroBee, the
PC or Cloud.
Unit (AgroBee | PC):
• AgroBee: when the Agrónic does not have commu-
nication with the AgroBee, the determining factor
is activated. The determining factor only aects
programs that have sectors with outputs assigned
to the AgroBee.
• PC: when the Agrónic does not have communi-
cation with the PC or the Cloud, the determining
factor is activated.
Module (00 ... 20): when the unit is the AgroBee, enter
the AgroBee number. The determining factor is
activated when there is no communication with any of
the AgroBee-Ls (leaving it at 0) or with the AgroBee-L
configured here.
User (0 ... 3): when the unit is the PC, enter the user
number. The determining factor is activated when
there is no communication with any of the users
(leaving it at 0) or with the user configured here. For
communication with the Cloud, enter user 3.
DETERMINING FACTOR PARAMETERS
Determining factor: 02 Type: conditional stop
Origin: digital sensor
Digital sensor No.: 04
Delay, detection: 0110”
Origin: communication
Unit: agroBee
Module: 01
Origin: analog sensor
Analog sensor No.: 01
Delay, detection: 0150”
Reference: 05.2 Bar
Dierential: 01.0 Bar
When surpassed: yes
Origin: meter sensor
Meter sensor No.: 01
Delay, detection: 0015”
at start: 0300”
Reference: 008.50 m3/h
When surpassed: no