Parameters | Determining factors
5.6.7 Filter pressure gage
A dierential pressure gage is needed to start filter
cleaning when the pressure between the input and
output drops. This determining factor assigns the
pressure gage sensor to filter cleaning and activates
cleaning when the determining factor is activated.
Detection delay (0000 ... 9999”): the time that the deter-
mining factor must remain to activate or deactivate the
determining factor.
Origin: digital sensor
The determining factor is activated when the digital
sensor is activated for a period of time.
Origin: analog sensor
Reference: sensor value from which the determining
factor is activated or deactivated.
Dierential: margin between activation and deactiva-
tion of the determining factor.
When surpassed (Yes ... No):
• yes: if (value > reference) active determining factor.
If (value < reference – dierential) non-active
determining factor.
• No: if (value < reference) active determining factor.
If (value > reference + dierential) non-active
determining factor.
DETERMINING FACTOR PARAMETERS
Determining factor: 18
Origin: digital sensor
Digital sensor No.: 02
Delay, detection: 0030”
Origin: analog sensor
Analog sensor No.: 01
Delay, detection: 0030”
Reference: 04.3 bar
When surpassed: yes