31
Parameters | Determining factors
User Manual | Agrónic 2500
5.6.4 Warning
The Warning does not act on programs. It only makes
a record when it is activated and when it is deactivat-
ed. This record can be used to send an SMS, but it only
sends SMS when the alert is activated, not when it is
deactivated. With the warnings, anti-the, anti-freeze,
warn about pipe breaks, errors in meters, etc. can be
configured.
Detection delay (0000 ... 9999”): the time that the deter-
mining factor must remain in order to activate or deac-
tivate the determining factor.
Origin: digital sensor
The determining factor is activated when the digital
sensor is activated for a period of time.
Origin: analog sensor and meter sensor
Reference: sensor value from which the determining
factor is activated or deactivated.
Dierential: margin between activation and deactiva-
tion of the determining factor.
When surpassed (Yes ... No):
• yes: If (value > reference) active determining factor.
If (value < reference – dierential) non-active
determining factor.
• No: If (value < reference) active determining factor.
If (value > reference + dierential) non-active
determining factor.
Origin: flow error
High margin (000 ... 100 %): the determining factor is
activated when the instantaneous flow rate is higher
than the expected flow rate in this % (At 0 there is no
high margin control).
Low margin (000 ... 100 %): the determining factor is
activated when the instantaneous flow rate is lower
than the expected flow rate in this % (At 0 there is no
low margin control).
Start-up delay (0000 ... 9999”): when a program
starts during this time, the determining factor is not
calculate).
Margin detection delay (0000 ... 9999”): time that the
high margin or low margin determining factor must
remain to activate or deactivate the determining factor.
Delay with no pulse (000 ... 255’): time in minutes that
must transpire without receiving pulses from the meter
to activate the determining factor (At 0 there is no
meter error control).
Reference for leak (000.00 ... 655.35): if there is no ir-
rigation order that the meter uses, the leak will be
controlled by issuing a warning when the leak flow
reference is exceeded (At 0 there is no leak control).
Leak delay (000 ... 255’): minutes that the leak flow
must remain for the warning to be given.
DETERMINING FACTOR PARAMETERS
Determining factor: 01 Type: warning
Origin: digital sensor
Digital sensor No.: 01
Delay, detection: 0030”
Origin: analog sensor
Analog sensor No.: 01
Delay, detection: 0150”
Reference: 01.8 Bar
Dierential: 01.0 Bar
When surpassed: no
Origin: meter sensor
Meter sensor No.: 01
Delay, detection: 0000”
Reference: 020.00 m3/h
Dierential: 001.00 m3/h
When surpassed: no
Origin: flow error
Meter sensor No.: 01
High margin: 015%
Low margin: 019%
Delay, at start: 0120”
Detection margins: 0030 ”
Delay without pulse: 006 ‘
Ref. for leak: 000.00 m3/h
Leak delay: 000 ‘