Parameters | Determining factors
5.6.1 Definitive stop / Temporary stop
Definitive stop
Stops associated programs until manually reset.
To reset it, go to ‘Function - 2. Manual - 6. Terminate
stops’. When it is reset, it also asks whether to continue
with the programs that have been stopped from the
point where they were. It can only be activated if there
is an irrigation program associated.
Temporary stop
Pauses associated programs until the next start. The
irrigation units remaining in the program are lost. It
can only be activated if there is an irrigation program
associated.
Detection delay (0000 ... 9999”): the time that the deter-
mining factor must remain to activate or deactivate the
determining factor.
Origin: digital sensor
The determining factor is activated when the digital
sensor is activated for a period of time.
Origin: analog sensor and meter sensor
Start-up delay (0000 ... 9999”): when a program starts
during this time, the determining factor is not calculat-
ed. In the case of sequential programs, it only applies
to the start of the first program.
Reference: sensor value from which the determining
factor is activated or deactivated.
When surpassed (Yes ... No):
• yes: the determining factor is activated if the
sensor value is higher than the reference (value >
reference).
• No: the determining factor is activated if the sensor
value is lower than the reference (value < reference).
DETERMINING FACTOR PARAMETERS
Determining factor: 01 Type: definitive stop
Origin: digital sensor
Digital sensor No.: 01
Delay, detection: 0030”
Origin: communication
Unit: agroBee
Module: 01
Origin: analog sensor
Analog sensor No.: 01
Delay, detection: 0150”
Reference: 01.8 Bar
When surpassed: no
Origin: meter sensor
Meter sensor No.: 01
Delay, detection: 0000”
at start: 0000”
Reference: 000.00 m3/h
When surpassed: no
Origin: flow error
Meter sensor No.: 01
High margin: 015%
Low margin: 019%
Delay, at start: 0120”
Detection margins: 0030 ”
Delay without pulse: 006 ‘
Origin: flow error
Start-up delay (0000 ... 9999”): when a program starts
during this time, the determining factor is not calculated.
High margin (000 ... 100 %): the determining factor is
activated when the instantaneous flow rate is higher
than the expected flow rate in this % (At 0 there is no
high margin control).
Low margin (000 ... 100 %): the determining factor is
activated when the instantaneous flow rate is lower
than the expected flow rate in this % (At 0 there is no low
margin control).
Delay with no pulse (000 ... 255’): time in minutes that
must transpire without receiving pulses from the meter
to activate the determining factor (At 0 there is no meter
error control).
Origin: communication
Use the communication status with the AgroBee, the
computer or Cloud.
Unit (AgroBee | PC):
• AgroBee: when the Agrónic does not have commu-
nication with the AgroBee, the determining factor
is activated. The determining factor only aects
programs that have sectors with outputs assigned to
the AgroBee.
• PC: when the Agrónic does not have communication
with the computer or the Cloud, the determining
factor is activated.
Module (00 ... 20): when the unit is the AgroBee, enter
the AgroBee number. The determining factor is activated
when there is no communication with any of the AgroBee-
Ls (leaving it at 0) or with the AgroBee-L configured here.
User (0 ... 3): when the unit is the PC, enter the user
number. The determining factor is activated when
there is no communication with any of the users
(leaving it at 0) or with the user configured here. For
communication with the Cloud, enter user 3.