Setback Schedules Page
Professional Series Network Thermostat Configuration Guide, Release 3.0 3-23
Part No. 600-01000-200, Rev. 2
Use Table 3-3 to modify the Occupied, Unoccupied, or Other Class Schedule page
fields.
Table 3-3 Occupied (Unoccupied or Other) Class Schedule Field Descriptions
Field Description
Period Displays one of four time periods of the day.
Time Use the drop-down menu to modify the time period in 15 minute increments.
Includes AM / PM indicator. Note: You can modify the time period in 5
minute increments on the NT130e/h and NT160e/h models only.
Heat (Temp) Use the drop-down menu to select a heat temperature setback setting
between 40
°
F(3.5
°
C) to 99
°
F(36
°
C).
Cool (Temp) Use the drop-down menu to select a cool temperature setback setting
between 40
°
F(3.5
°
C) to 99
°
F(36
°
C).
Fan Sche(dule) Select the time in each hour of the Period in which the fan will be On. The
schedule begins on the hour and advances for the duration specified. Note
that within the hour of each Period but outside the schedule interval, the fan
reverts to AUTO mode to ensure proper operation for either a heating or
cooling call to the HVAC system. Select one of the following options:
Disable/Off (default) – No fan operation scheduled within this Period.
On – Fan is forced On for the entire hour, for every hour, within this
Period.
15, 30, 45 minutes – Fan is forced On for this selected duration,
beginning at the top of the hour, for every hour, within this period.
Relay Sched
(NT160e/h only)
Select the time in each hour of the Period in which the External Relay
Trigger will be On. The schedule begins on the hour and advances for the
duration specified. Select one of the following options:
Off (default) – No External Relay Trigger scheduled within this Period.
On – External Relay Trigger is forced On for the entire hour, for every
hour, within this Period.
15, 30, 45 minutes – External Relay Trigger is forced On for this
selected duration, beginning at the top of the hour, for every hour, within
this Period.