Advanced Settings Page
Professional Series Network Thermostat Configuration Guide, Release 3.0 3-39
Part No. 600-01000-200, Rev. 2
Auxiliary Heat Specifies a secondary source of heat outside the heat pump
system, for example, electric baseboard or a gas furnace.
Disable – Disables Auxiliary Heat.
Enable w/ Comp – Enables the compressor when Auxiliary
Heat is active.
Enable w/o Comp – Disables the compressor when
Auxiliary heat is active.
Aux Heat Offset Specifies the auxiliary heat set point temperature referenced to
the first stage heat set point temperature. This parameter is only
enabled when Auxiliary Heat is enabled, otherwise it is
disabled. (e.g. If the first stage temperature set point is set to
70°F, and this parameter were set to -3°F, the auxiliary heat
would activate at or below 67°F). Temperatures include:
0,-2, -3, -4, -5, -6
°
F (0,-1.0, -1.5, -2.0, -2.5, -3.0
°
C) – Second
stage heat temperature offset from first stage heat set point
temperature.
Cool Control Specifies the HVAC control of this thermostat. This parameter
describes the thermostat’s capability to control a heat pump
system. The thermostat can also be disabled from controlling a
cooling system and instead operate as a heat-only thermostat.
(See Heat Control (page 3-37).)
Disable – Specifies that there is no cooling system present.
(Heat only thermostat.)
2C – Enables the heat pump as a standard dual stage cooling
system.
1C – Enables the heat pump as a standard single stage
cooling system.
2
nd
Stage Offset
Specifies a secondary source of cool air outside the heat pump
system, for example, electric baseboard or a gas furnace.
This parameter is only enabled when 2C Cool Control is
enabled, otherwise it is disabled.
0, +2, +3, +4, +5, +6
°
F (0, +1.0, +1.5, +2.0, +2.5, +3.0
°
C).
Thermostat Configuration
Hold Mode Duration
(NT100e/h, NT120e/h, and
NT150e/h only)
Specifies the time interval in which the thermostat temperature
setting are held independent of schedule changes due to Period
or Day Class advancements.
Perm – The Hold period is indefinite and the temperature
setting are “held” until the user removes this condition.
1, 3, 8, 12, 24 –The amount of time in hours in which the
current temperature setting are “held” and inhibited from
change. The default interval is 3 hours.
Table 3-6 Advanced Settings Fields - HVAC Fuel Burner Field Descriptions