3-48 Professional Series Network Thermostat Configuration Guide, Release 3.0
Part No. 600-01000-200, Rev. 2
CHAPTER 3: Configuring the Thermostat Using the TMI
Sensor Averaging Select Enable or Disable to indicate if this remote thermal
sensor is to participate in the algebraic averaging of either or
both of the thermostat (local) sensor or the remaining Remote
Sensor. This parameter is visible only if the Remote Sensor
#1/#2 State is enabled. (See Zone Temperature (page 3-10).)
Disable (default) – Algebraic thermal averaging is disabled.
Enable – Remote Sensor #1/#2 is included in the thermal
averaging calculations. The Zone temperature now reflects
the average temperature of the averaged measurements.
Sensor Correction Indicate the calibration or temperature offset compensation for
this remote thermal sensor. Offset adjustments are added or
subtracted from the actual temperature read from this sensor and
displayed as the apparent temperature. This apparent
temperature is available for averaging with the other sensors if
Sensor Averaging is selected.
-5
°
F (-2.8
°
C) through +5
°
F (2.8
°
C) – Offset temperature in
degrees Fahrenheit or Celsius increments. The default is 0.
Table 3-7 Sensor Settings Field Descriptions (Continued)