4.5.3 DULCO flex Control DFXa, DFXa data objects
Tab. 39: Status and control
Module
/ slot
Index Name Module
name
Identifi‐
cation
(hex)
Type Data
flow *
Description
bit Name Function
1 1 State Status 40.83 u32 R 0 Motor Motor state
0 = Motor idle,
1 = Motor running
1 System
Ready
Flag
1 = pump ready
to start
2 ... 4 Mode 00 – halt
01 – manual
02 – batch
03 – contact
04 – analogue
5 Error There are errors -
see “Errors”
6 Warn‐
ings
There are warn‐
ings - see “Warn‐
ings”
7 Manual
stop
Pump has been
stopped manually
8 Stop Pump has
stopped
9 Priming Pump is in pri‐
ming mode
(higher-level
function)
10 Auxil‐
iary
Pump is in auxil‐
iary mode
(higher-level
function)
11 Pause Pump has been
switched to
‘Pause’
status
(higher-level
function)
12 Module Fieldbus active
13 Hose
change
Hose is being
changed
14 Batch
Mem.
Batch memory is
activated
15 Cali‐
brated
Pump is cali‐
brated
Supplementary operating instructions for PROFINET
®