12
CONSOLE CALIBRATION
1. CALCULATING OFFSETS
The offsets need to be set if the system is controlled by a PWM Valve and C-P was selected
during initial console programming.
1) ANTI-ICE HIGH OFFSET
a) LIQ display will show "oFS". Left DATA display will show "Anhi". Right
DATA display will show "254".
b) Depress
.
c) Depress
to start running the liquid pump. The vol/min of liquid
and "Anhi" will alternately be displayed in the left DATA display.
While liquid pump is running, depress and hold
until the vol/min
begins to decrease. Depress
to slowly increase the vol/min until
the maximum vol/min is noticed, then increase offset value displayed in
the right DATA display by an additional 10.
d) After desired offset value is set, depress
. HIGH OFFSET is now set.
e) Depress
to advance to ANTI-ICE LOW OFFSET.
2) ANTI-ICE LOW OFFSET
a) LIQ display will show "oFS". Left DATA display will show "AnLo". Right
DATA display will show "2".
b) Depress
.
c) Depress
and the liquid pump will stop running. The vol/min of the
liquid and "AnLo" will alternately be displayed in the left DATA display.
Depress and hold
until the pump starts running. Use to slowly
decrease the vol/min until "0000" is displayed, then decrease offset value
displayed in the right DATA display by an additional 10.