— English Reflexomat with Touch controller — 06.07.2016 - Rev. B
07 Make-up cycles – • Set value exceeded.
• Leakage in the
system.
•
Check set value in the Customer
or Service menu.
• Seal any leak in the system.
"OK"
08 Pressure
measurement
– Controller receives
incorrect signal.
• Connect the plug.
• Check functioning of the
pressure sensor.
• Check the cable for damage.
"OK"
09 Level sensor – Controller receives
incorrect signal.
• Check functioning of the load
cell.
• Check the cable for damage.
• Connect the plug.
"OK"
10 Maximum pressure – • Set value exceeded.
• Overflow line
disabled.
• Dirt trap clogged.
•
Check set value in the Customer
or Service menu.
• Check functioning of the
overflow line.
• Clean the dirt trap.
"OK"
11 Make-up quantity – Only if "With water meter"
is activated in the
Customer menu.
• Set value exceeded.
• Severe water loss in
the system.
•
Check set value in the Customer
or Service menu.
• Check water loss in the system
and repair, if necessary.
• Water quantity per contact
incorrectly set in the Service
menu.
"OK"
15 Make-up valve – Contact water meter
measures without make-
up request.
• Check the "WV" make-up valve
for leaks.
"OK"
16 Power failure – No power. Connect to power supply. –
19 Stop > 4 h – Device is in Stop mode for
more than 4 hours.
Set the controller to Automatic
mode.
–
20 Max. Make-up
volume
– Set value exceeded. Reset the "Make-up quantity" meter
in the Customer menu.
"OK"
21 Maintenance
recommended
– Set value exceeded. Carry out maintenance. "OK"
24 Softening – • Set value for soft
water capacity
exceeded.
• Time interval for
replacement of the
softening cartridge
exceeded.
Replace the softening cartridges. "OK"
30 I/O module fault – • I/O module defective.
• Connection between
option card and
controller faulty.
• Option card defective.
Inform Reflex Customer Service. –