70 Rockwell Automation Publication MOTION-AT007A-EN-P - May 2020
Appendix A Kinetix and PowerFlex Drive Specifications
The attached table identifies the fuses tested, the actual circuit parameters and the circuit configuration. In the attached table, the
Interrupting Amps column specifies the fuses minimum and maximum amps that the fuse will safely clear at 810V DC.
By way of this correspondence, Cooper Bussmann self-certifies the preceding fuses in end-user applications to the preceding parameters
and the attached data sheet.
Should you have any questions regarding this correspondence, please contact me at the listed address and numbers.
Regards,
Strategic OEM Accounts Manager
Cooper Bussmann
Table 63 - Cooper Bussmann 170M, DC Fuse Test for Rockwell Automation
Fuse Results
Circuit Parameters
Interrupting Amps
Volts DC Time Constant Circuit Configuration
Min Max
170M6646 Acceptable – 69.8 kA 812 2 ms Configuration A
170M6646 Acceptable 10.2 kA – 812 1.66 ms Configuration A
170M6650 Acceptable – 69.6 kA 812 2 ms Configuration A
170M6650 Acceptable 21.1 kA – 812 1.2 ms Configuration A
170M7510 – – 65 kA 810 2 ms –
170M7510 – 20 kA – 810 2 ms –
170M6792 – – 65 kA 810 2 ms –
170M6792 – 19 kA – 810 2 ms –
170M6793 – – 65 kA 810 2 ms –
170M6793 – 23 kA – 810 2 ms –
170M6794 – – 65 kA 810 2 ms –
170M6794 – 27.5 kA – 810 2 ms –
170M6828 – – 65 kA 810 2 ms –
170M6828 – 37 kA – 810 2 ms –
170M6934 Acceptable – 105.4 kA 810 1.8 ms Configuration A
170M6934 Acceptable 45.2 kA – 810 1.12 ms Configuration A
170M7560 – – 100 kA 810 2 ms –
170M7560 – 60 kA – 810 2 ms –
Circuit Configuration A
Fuse Fuse