E.3.5
E.3.6
SEN-60204-1,
Part
15.2.2:
Identification
of
the
Protective
Conductor
For
insulated
conductors,
the
two-color
combination
of
green
and
yellow
should
meet
the
following
criteria
for
any
given
15
mm
length:
one
of
the
colors
should
cover
at
least
30%
and
no
more
than
70%
of
the
surface,
with
the
other
color
covering
the
remainder
of
the
surface.
Operator
Control
Stations
The
enclosure
of
an
operators
control
station
must
be
constructed
of
a
conductive
metal.
The
cover
of
the
enclosure
should
be
bonded
to
the
case
and
not
rely
on
the
hinge
for
bonding.
Standard
industrial
operator
devices,
e.g.,
pushbuttons,
switches,
and
meters,
may
be
used.
The
wiring
connecting
the
operators
devices
to
the
drive
must
be
run
in
continuous,
rigid,
conductive
conduit,
continuously-screened
armored
cable, or
equivalent.
Note
that
the
use
of
flexible
metal
conduit,
open
wire,
or
wire
in
trays
is
not
acceptable.
Many
flexible
metal
conduit
products
have
not
been
designed
for
RF
containment
and
are
not
adequate
to
maintain
compliance.
Proper glands
must
be
used
to
terminate
the
operators
control
station
conduit/cable
at
the
station
and
the
drive.
The
gland
must
secure
the
cable
screen
to
the
conductive
surfaces
of
the
drive
and
station
enclosure.
A
full
360°
screen
termination
is
preferred.
Screen
pigtails
are
not
permitted.
I/O
Signals
Control
(I/O)
and
signal
wiring
must
be
run
in
continuous,
rigid,
conductive
conduit
or
continuously-screened
cable
as
shown
in
figure
E.4.
Note
that
the
use
of
flexible
metal
conduit,
open
wire,
or
wire
in
trays
is
not
acceptable.
Many
flexible
metal
products
have
not
been
designed
for
RF
containment
and
are
not
adequate
to
maintain
compliance.
Stranded
copper
wire
i
Plastic
insulation
Inner
plastic
sheath
Compact
screen
of
galvanized
(tinned)
copper
or
steel
braid
Outer
plastic
jacket
Figure
E.4
-
I/O
Signal
Cable
Compliance
with
Electromagnetic
Compatibility
Standards
E-7