3.3
Selecting
Input
AC
Line
Branch
Circuit
Fuses
ATTENTION:
Most
codes
require
that
upstream
branch
circuit
protection
be
provided
to
protect
input
power
wiring.
Install
the
fuses
recommended
in
table
3.9.
Do
not
exceed
the
fuse
ratings.
Input
line
branch
circuit
protection
fuses
must
be used
to
protect the
input
power lines.
See
figure
5.1.
Table
3.9
shows
recommended
fuse
values.
These
fuse
ratings
are
applicable
for
one
drive
per
branch
circuit.
No
other
load
may
be
applied
to
that
fused
circuit.
Note
that
contactors
and
circuit
breakers
are
not
recommended
for
AC
input
line
branch
protection.
Table
3.9
AC
Input
Line
Fuse
Selection
Values
Model
Fuse
Model
Fuse
Model
Fuse
Number
Rating*
Number
Rating*
Number
Rating*
1SU11001
20A
1SU41001
6A
1SU51001
4A
1SU14001 12A 1SU44001
6A
1SU54001
4A
1SU41002
8A
1SU51002
7A
1$U21001 10A
1SU44002
8A
1SU54002
7A
1SU24001 10A
1SU41003
12A
1SU51003
10A
1$U21002
30A
1SU44003
12A
1SU54003
10A
1SU41005
25A
1SU51005
15A
1SU21001 12A
1SU44005
25A
1SU54005
15A
1SU24001 12A
1SU41007 25A 1SU51007 20A
18U21002
20A 1SU44007 25A 1SU54007
20A
1SU24002
20A
1SU41010
35A
1SU51010
25A
1SU21003
25A
1SU44010
35A
1SU54010
25A
1SU24003
25A
1SU41015
45A
1SU21005
35A
1$U42015
45A
1SU24005
35A
1SU41020
55A
1$U42020
55A
*
Recommended
fuse
type:
UL
Class
J,
600V,
time-delay,
or
equivalent.