Rockwell Automation RELIANCE ELECTRIC SP500 - 6.2 Checking Drive Operation

Rockwell Automation RELIANCE ELECTRIC SP500
122 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Step
9.
Step
10.
Step
11.
Step
12.
Step
13.
Step
14.
Step
15.
Step
16.
Step
17.
Check
that
the
wire
sizes
are
within
terminal
specifications
and
that
the
terminals
are tightened
to
the
appropriate
torque
specifications.
Refer
to
tables
3.2
through
3.6.
Check
that
the
user-supplied
branch
circuit
protection
is
installed
and
correctly
rated.
Check
that
the
incoming
AC
power
is
rated
correctly.
Check
the
motor
installation
and
length
of
motor
leads.
Disconnect
any
power
correction
capacitors
connected
between
the
drive
and
the
motor.
Check
that
any
motor
thermal
switch
and
the
drive’s
electronic
thermal
overload
are
enabled
(parameter
F-15
=
ON).
Check
that
the
rating
of
the
transformer
(if
used)
matches
the
drive
requirements
and
is
connected
for
the
proper
voltage.
Verify that
a
properly-sized
ground
wire
is
installed
and
that
a
suitable
earth
ground
is
used.
Check
for
and
eliminate
any
grounds
between
the
motor
frame
and
the
motor
power
leads.
Verify
that
all
ground
leads
are
unbroken.
Uncouple
the
motor
from
any
driven
machinery
to
initially
start
the
drive.
6.2
Checking
Drive
Operation
ATTENTION:
DC
bus
capacitors
retain
hazardous
voltages
after
input
power
has
been
disconnected.
After
disconnecting
input
power,
wait
five
(5)
minutes
for
the
DC
bus
capacitors
to
discharge
and
then
check
the
voltage
with
a
voltmeter
to
ensure
the
DC
bus
capacitors
are
discharged
before
touching
any
internal
components
Use
the
following
procedure
to
check
the
operation
of
the
drive:
Step
1.
Step
2.
Step
3.
Step
4.
Step
5.
Step
6.
Turn
off,
lock
out,
and
tag
power
to
the
drive.
Wait
five
minutes.
Remove
the
cover
and
check
the
DC
bus
potential
with
a
voltmeter
as
described
in
section
9.1.
Verify that
the
DC
bus
capacitors
are
discharged.
Replace
the
cover.
Uncouple
the
driven
equipment
from
the
motor,
if
possible.
Apply
power
to
the
drive.
SELF
should
be
displayed
for
approximately
1
to
2
seconds
to
indicate
internal
diagnostics
are
being
performed.
After
1
to
2
seconds,
0
should
be
displayed
and
the
LEDs
should
indicate
drive
status.
If
any
fault
codes
are
displayed,
refer
to
chapter
9,
Troubleshooting
Reference.
Check
all
parameter
settings
and
verify
that
they
are
set
correctly
based
on
the
application.
In
most
cases,
the
factory
default
values
are
adequate
for
this
no-load
start-up
test.
Parameters
are
described
in
chapter
8.
Press
the
START
key.
The
drive
should
ramp
at
the
acceleration
rate
(F-01)
until
it
reaches
the
preset
minimum
speed
(F-03).
6-2
SP500
AC
Drive
Installation
and
Operation
Manual
Version
3.1