3.1
SP500
System
Planning
This
chapter
provides
information
that
you
must
consider
when
planning
an
SP500
drive
installation.
Installation
site,
wiring,
and
motor
application
requirements
are
included.
ATTENTION:
Only
qualified
electrical
personnel
familiar
with
the
construction
and
operation
of
this
equipment
and
the
hazards
involved
should
install,
adjust,
operate,
or
service
this
equipment.
Read
and
understand
this
manual
and
other
applicable
manuals
in
their
entirety
before
proceeding.
ATTENTION:
Use
of
power
correction
capacitors
on
the
output
of
the
drive
can
result
in
erratic
operation
of
the
motor,
nuisance
tripping,
and/or
permanent
damage
to
the
drive.
Remove
power
correction
capacitors
before
proceeding.
ATTENTION:
The
user
is
responsible
for
conforming
with
all
applicable
local,
national,
and
international
codes.
Installation
Site
Requirements
It
is
important
to
properly
plan
before
installing
an
SP500
drive
to
ensure
that
the
drives
environment
and
operating
conditions
are
satisfactory.
Note
that
no
devices
are
to
be
mounted
behind
the
drive.
This
area
must be
kept
clear
of
all
control
and
power
wiring.
Read
the
following
recommendations
before
continuing
with
the
drive
installation.
Before
deciding
on
an
installation
site,
consider
the
following
guidelines:
*
The
area
chosen
should
allow
the
space
required
for
proper
airflow
as
specified
in
sections
3.1.1
and
3.1.2.
*
Do
not
install
the
drive
above
1000
meters
(3300
feet)
without
derating
output
power.
For
every
91.4
meters
(300
feet)
above
1000
meters
(8300
feet),
derate
the
output
current
by
1%.
*
Verify that
the
drive
location
will
meet
the
following
environmental
conditions:
Operating
temperature
(ambient):
0
to
+40°C
(32
to
104°F)
Storage
temperature
(ambient):
40
to
+65°C
(40
to
+149°F)
Humidity:
5
to
95%
(non-condensing)
*
Verify that
NEMA
1
drives
can
be
kept
clean,
cool,
and
dry.
*
Be
sure
NEMA
1
drives
are
located
away
from
oil,
coolants,
or
other
airborne
contaminants.
*
Verify that
the
AC
power
distribution
system
meets
the
service
conditions
specified
in
table
A.1.
SP500
System
Planning
3-1