3.1.2
Providing
Proper
Air
Flow
Clearances
Be
sure
there
is
adequate
clearance
for
air
ventilation
around
the
drive.
For
best
air
movement,
do
not
mount
SP500
drives
directly
above
each
other.
Note
that
no
devices
are
to
be
mounted
behind
the
drive.
This
area
must
be
kept
clear
of
all
control
and
power
wiring.
See
table
3.1
for
listing
of
the
recommended
air
flow
clearances.
Table
3.1
Air
Flow
Clearances
Enclosure
A
B
Cc
D
Minimum
distance
from
the
sides
of
the
drive
if
adjacent
to
non-heat
51mm
|}102
mm|
102 mm}
102
mm
producing
equipment
(2) (4)
(4°)
(4)
Minimum
distance
from
the
top
and
bottom
of
the
drive
if
adjacent
to
102
mm/102
mm]
102 mm|
102
mm
non-heat
producing
equipment
(4) (4) (4) (4)
Minimum
distance
from
the
sides
of
the
drive
if
adjacent
to
other
drives
51
mm
102
mm]
102
mm|
102
m
(2) (4) (4) (4)
Minimum
distance
from
the
top
and
bottom
of
the
drive
if
adjacent
to
254
mm|
254
mm]
254
mm}
102
m
other
drives
(10)
(10) (10)
4)
3.1.3
3.2
3.2.1
3.2.2
Verifying
the
Drives
Power
Loss
Rating
When
installing
an
SP500
drive
inside
of
another
enclosure,
you
should
consider
the
drives
watts
loss
rating
shown
in
table
2.2.
This
table
lists
the
typical
full
load
power
loss
watts
value
under
all
operating
carrier
frequencies.
Ensure
adequate
ventilation
is
provided
based
on
the
drives
watts
loss
rating.
Wiring
Requirements
Evaluate
the
following
areas
of
drive
wiring
before
you
do
the
installation:
size
of
available
conduit,
size
of
power
and
control
wiring,
and
motor
lead
lengths.
Verifying
Conduit
Sizes
Itis
important
to
determine
the
size
of
the
conduit
openings
accurately
so
that
the
wire
planned
for
a
specific
entry
point
will
fit
through
the
opening.
Figures
4.1
through
4.4
show
conduit
opening
sizes.
Recommended
Power
Wire
Sizes
Size
input
power
wiring
according
to
applicable
codes
to
handle
the
drives
continuous-rated
input
current.
Size output
wiring
according
to
applicable
codes
to
handle
the
drives
continuous-rated
output
current.
Tables
3.2, 3.3,
and
3.4
provide
recommended
power
wiring
sizes.
Use
only
copper
wire
with
a
minimum
temperature
rating
of
60/75°C.
Table
3.5
contains
the
recommended
tightening
torque
values
for
all
power
wiring
terminals.
3-4
SP500
AC
Drive
Installation
and
Operation
Manual