Rockwell Automation RELIANCE ELECTRIC SP500 - 9.3 Accessing and Clearing the Error Log

Rockwell Automation RELIANCE ELECTRIC SP500
122 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
OL
=
ELECTRONIC
THERMAL
OVERLOAD
The
electronic
thermal
overload
trip
level
has
been
exceeded.
This
fault
protects
the
drive
motor
from
overheating
due
to
excessive
current
within
a
specified
period.
Note
that
the
fault
will
not
clear
until
the
input
line
voltage
is
within
the
proper
range.
This
may
take
a
few
seconds.
Possible
Cause
Corrective
Action
The
current
limit
setting
in
F-05
is
incorrect.
The
electronic
thermal
overload
setting
in
F-14
does
not
match
the
motor
and
drive
combination.
If
the
current
limit
level
is
too
low
relative to
the
load,
increase
the
current
level
in
F-05.
Refer
to
chapter
8
for
the
parameter
description.
Verify
the
value
of
F-14.
Refer
to
chapter
8
for
the
parameter
description.
elec
=
POWER
SUPPLY
OUT
OF
RANGE
The
power
supply
is
out
of
range.
Possible
Cause
Corrective
Action
Possible
regulator
failure.
Contact
Reliance
Electric
for
assistance
if
the
fault
reoccurs
after
pressing
the
STOP/RESET
key
(or
asserting
the
IET
reset
input)
or
cycling
power.
SELU
=
INVALID
DRIVE
VOLTAGES
The
value
in
F-28
is
incorrect
for
the
drive.
Possible
Cause
Corrective
Action
An
invalid
drive
voltage
was
selected
in
F-28.
Select
the
voltage
to
match
the
input
line
voltage.
9.3.
Accessing
and
Clearing
the
Error
Log
If
a
fault
occurs,
the
drive
displays
a
fault
code
and
logs
the
fault
code
into
the
error
log.
If
more
than
one
fault
occurs,
the
first
fault
flashes
on
the
display
and
the
subsequent
faults
(up
to
two)
are
logged
in
the
error
log.
After
three
faults,
no
subsequent
faults
are
logged.
The
faults
in
the
error
log
are
numbered
sequentially.
For
example,
if
an
overcurrent
fault
occurred
first
followed
by
a
thermal
overload
fault,
the
error
log
would
read
1-OC,
2-OL.
The
last
fault
to
occur
appears
first
when
the
error
log
is
accessed.
For
example,
if
the
last
fault
to
occur
was
a
low
bus
fault,
and
the
error
log
contained
three
entries,
the
error
log
would
display
3-LU
when
the
error
log
is
accessed.
Troubleshooting
Reference
9-5

Table of Contents

Related product manuals