F-18
RPM
Setpoint
Enable
The
parameter
enables
the
setpoint
to
be
displayed
in
F-08
units.
Parameter
Range:
OFF
=
Setpoint
is
displayed
in
hertz.
ON
=
Setpoint
is
displayed
in
the
units
specified
in
F-08.
Default
Setting:
ON
Step
Size:
N/A
If
F-18
=
ON,
pressing
the
~@
and
‘~W
keys
will
change
the
setpoint
in
units
of
4
between
minimum
speed
in
F-08
units
and
maximum
speed
in
F-08
units.
Note
that
this
parameter
only
affects
the
setpoint,
not
the
display.
Example
Assume
a
drive
is
currently
running
at
60
Hz
=
1750
RPM,
F-08 =
1750,
and
F-10
=
ON.
When
the
“WW
key
is
pressed,
1750
is
displayed.
When
the
“WW
key
is
pressed
three
more
times,
the
display
will
change
from
1750
to
1749
to
1748
to
1747.
The
reference
is
then
rescaled
based
on
this
input:
Reference
(1747)
Input
Reference
=
x
F-04
(60
Hz)
= 59.89
Hz
F-08
(1750)
F-19
Power-Up
Start
Enable
This
parameter
determines
whether
the
motor
starts
Parameter
Range:
OFF
=
Motor
does
not
start
at
drive
power
up.
ON
=
Motor
starts
at
drive
power
up.
automatically
when
the
Default
Setting:
OFF
drive
is
powered
up.
Step
Size:
N/A
ATTENTION:
Setting
F-19
=
ON
causes
output
power
to
be
applied
to
the
motor
automatically
at
drive
power
up.
When
this
function
is
enabled,
the
user
must
ensure
that
automatic
start
up
of
the
driven
equipment
will
not
cause
injury
to
operating
personnel
or
damage
to
the
driven
equipment.
In
addition,
the
user
is
responsible
for
providing
suitable
audible
or
visual
alarms
or
other
devices
to
indicate
that
this
function
is
enabled
and
the
drive
may
start
at
any
moment
When
F-19
=
ON,
output
power
is
applied
to
the
motor
at
drive
power
up
if
the
following
conditions
are
met:
*
The
drive
power-up
diagnostics
must
be
passed
(SELF
will
be
displayed
at
power
up).
*
No
faults
can be
active.
*
The
terminal
strip
function
loss
input
must be
closed.
*
The
front-panel
keypad
STOP/RESET
key
must
not
be
pressed.
If
the
drive
is
under
local
control,
it
will
effectively
simulate
a
start
signal
to
start
the
drive.
If
the
drive
is
under
remote
control,
the
drive
will
start
only
if
the
terminal
strip
START
input
is
asserted.
Programming
Reference
8-13

Table of Contents